GRIDSCAN® 5000
COMPREHENSIVE TRANSFORMER MONITORING
Protect critical transformer assets without worrying about maintaining sensors or calibration. GRIDSCAN 5000 Series
analyzers provide an accurate, reliable and affordable hydrogen process gas measurement solution for the insulating liquid or headspace of power transformers.
Certi昀椀cations: The GRIDSCAN 5000 meets all relevant global monitoring standards for transformer installations and is
CE-approved for safe general-use operation.
Speci昀椀cations
Hydrogen Sensor Speci昀椀cations
H2 Measurement Range
Oil Phase: 25 - 5,000 ppm
Gas Phase: 25 - 5,000 ppm in-oil equivalent
Repeatability1
±10% of reading or ±15 ppm, whichever is greater
Response Time
< 60 minutes
Operating Temperature
(Ambient)
-40°C to 70°C (-40°F to 158°F)
Storage Temperature
-40°C to 85°C (-40°F to 185°F)
Temperature Range2
Oil Phase: -40°C to 105°C (-40°F to 221°F)
Gas Phase: -40°C to 80°C (-40°F to 176°F)
Data Log Storage
1 year
Cross-sensitivity to H2O,
CO2, C2H2, C2H4, CO, etc.