H2scan TM Catalog 2025 - Flipbook - Page 13
GRIDSCAN® 6000
MULTI-SENSE MONITOR
Imagine knowing the condition of all your transformers, not just the select few. Imagine knowing, based on real data,
where to focus your Capital and O&M spend. And imagine getting that without increasing your maintenance budget.
The GRIDSCAN 6000 from H2scan makes that a reality by combining hydrogen, moisture, pressure and temperature
measurements in one reliable, long-lasting and maintenance-free monitoring package.
Certi昀椀cations: The GRIDSCAN 6000 meets all relevant global monitoring standards for transformer installations.
Sensors Performance Parameters
Operating Conditions
Insulating Liquid Temperature
Hydrogen
Operating
-20°C to 105°C (-4°F to 221°F)
Measurement Range
25 to 5000 ppm
Survival
-20°C to 135°C (-4°F to 275°F)
Accuracy
±20% of reading or ±25 ppm, whichever is greater
Insulating Liquid Supported
Mineral oil, silicone, natural ester,
synthetic ester
Repeatability
±10% of reading or ±15 ppm, whichever is greater
Response Time