H2scan TM Catalog 2025 - Flipbook - Page 11
GRIDSCAN® 5015
COMPREHENSIVE TRANSFORMER MONITORING
Protect critical transformer assets without worrying about maintaining sensors or calibration. GRIDSCAN 5015 sensor provide an
accurate, reliable, and affordable hydrogen gas measurement solution for power transformers and ancillary liquid 昀椀lled equipment.
Certi昀椀cations: The GRIDSCAN 5015 meets all relevant global monitoring standards for transformer installations and is
CE-approved for safe general-use operation.
Speci昀椀cations
Hydrogen Sensor Speci昀椀cations
1
H2 Measurement Range
Accuracy
250- 50,000 ppm
Physical Speci昀椀cations
± 20% of reading or ± 250 ppm
3
Wetted Materials
and Internal Sealing
316SS, 40% mineral 昀椀lled nylon, polyimide, viton
(昀氀uoropolymer elastomer), hermetic glass-to-metal
feed-through
External Housing
and Sealing
Hard anodized 6061 aluminum, 40% mineral 昀椀lled
nylon, viton (昀氀uoropolymer elastomer), nickel-plated
zinc (4-wire connector)
Humidity and
Corrosion Resistance6
(Ambient)
Class C5M marine equivalent; salt-water condensing
(IEC60068-2-11 & DIN EN ISO 12944)
Ingress Protection7
IP68; 7.62 m [25 ft.] water for 14 days (IEC 60529)
Certi昀椀cations
CE Mark, ROHS 2011/65/EU compliant, EMC/RFI and
Other Electrical Certi昀椀cation, IEC 55022 IFCC Part
15, IEC 55011, IEC 61000-4-2 through 61000-4-4,
61000-4-6, and 61000-4-8, IEC 61010-1, IEC 61326, IEC
60068-2-30
Vibration
3-axis Sinusoidal, Wide-band and Random
[Simulated Long-Life] (IEC 60068-2-6 table C.2, IEC
60068-2-64 paragraph A.2, category no. 2)
Shock
30 g, shock duration 18 ms (IEC 60068-2-27)
4M6, 4M4 (IBS), IEC 60721-3-4 ed.2 table 6
2
4
Repeatability5
± 10% of reading or ± 150 ppm4
Operating Temperature
(Ambient)
-20°C to 70°C (-4°F to 158°F)
Storage Temperature
-40°C to 85°C (-40° F to 185°F)
Gas Temperature Range
-40°C to 80°C (-40°F to 176°F)
Data Log Storage
1 year
Humidity
0-95% (non-condensing)
Cross-sensitivity to H2O,
CO2, C2H2, C2H4, CO, etc.